Contact us: +49 9321 2680 -201

PRODUCT DETAILS

TGA Box TÜV

TGA Box TÜV_DC Combiner

DC Combiner

with integrated safety devices
  • String collection and protection (up to 32 inputs)
  • DC isolator operated from outside/inside
  • String monitoring (optional)
  • Up to 1000V DC
  • TÜV certified

Application area

TGA Box TÜV DC Combiner Einsatzbereich

Technical Data

General Data

DC voltage

Max. 1000 V

DC short circuit current per input

Max. 7,5 A

DC Breaking & making capacity (according to EN60947-3)

200 A

Nominal current (I nom) per input

Max. 6,24 A

Short curcuit current

< 375A

Grounding (DC)

Floating positive and negative

Switch handle type

External handle (outside enclosure)

Housing

Installation

Outdoor / Indoor

UV resistance

Yes

Material

Polyester, fiberglass reinforced

Colour scheme

RAL 7035

Mounting

Wall

Dimensions & Weight

Housing (width/height/depth)

750/1000/320mm

Weight

50kg

Input parameters

Number of DC inputs

32 (+&- being one input)

Input cables

2,5mm² – 6mm²

Inputcables entrance through

Cable gland up to 10mm²

Fuse type

10x38mm

Location of fuses

Negative side or positive side / Negative side and positive side

Fuse link nominal current (I nom)

20 A

Fuse link time current characterisic

gPV (EN 60269-6)

Output parameters

Number of DC outputs

1x Plus / 1x Minus (+&- being one output)

Output cables

Max. 120 mm²

Output cables casing feed through

M40, cable outer Ø: 19-28 mm

RS-485 cables

0,5mm² – 2,5mm²

RS-485 cables

M20, cable outer Ø: 7-13 mm

Grounding connection

Min. 16 mm²

Grounding cable casing feed-through

M20, cable outer Ø: 7-13 mm

Monitoring

Values

Input current, voltage and temp.

Monitoring type

Measurement of two combined inputs

Power supply

24 VDC (6 A fuse required)

Standards

CE

Conform

Protection class and ambient conditions

Standards and regulations

EN 61439-2

Protection class in accordance with EN60529

IP 54

Permissible ambient temperature

-20 °C to +50 °C

Rel. humidity non-condensing

15% to 90%

Altitude above sea level

Max. 2.000 m

Additional properties

Surge protection

Typ 2 (auxiliary contact)

Optional

DC input cables casing feed through

MC4 (6 mm²)

DC switch disvonnector

Auxiliary contact

 

  • Application area
  • Technical Data
  • Download